  1. SafeTraces follow up meeting

    Sarthak Prasad and Morgan White are meeting with Sterling Laylock from SafeTraces on January 9 from 11 to 12 pm to cover the following:

    • Astronomy Building report findings and potential corrective action
    • Indoor Air Quality Monitoring specific to IT Security
      • UL 2905/UL 2906: Indoor Air Quality Sensor Performance/Sensor Deployment
      • UL Verified IoT Security
      • There is a newer building on campus that has CO2 sensors
        so we can discover what they did and follow that pathway
    • Our ongoing collaborative discussion with the State of Illinois' new Building Infrastructure
      Fund (2nd qtr 2023) where our work with you under iCAP is considered one of the missing pieces 
      of the puzzle.

      Their primary goal is to improve re-occupancy levels within existing buildings and cause new buildings (public and private) to design more effectively for IAQ/IEQ, especially where private development is receiving state funding and concessions.

      Since it was UL Healthy Buildings (Primary Partner of SafeTraces) that introduced IGT to
      the UL/SafeTraces ecosystem, ULHB will be instrumental in providing the capacity needed
      for our efforts with the state led by Illinois Chief Investment Officer, Joe Aguilar.
    • As discussed with Morgan at the end of our Design Thinking Session, Ikenberry Food Hall
      is being considered as our next project and UL Healthy Buildings ULHB is partnering with us
      on it since natural gas and hydrogen sulfide gas may be impacting IAQ/IEQ.
  2. Design Thinking Session Outcomes from the November 10, 2022 meeting

    Here's a short list of outcomes from our Nov 10th Design Thinking Session.

    • There a 2 more Design Thinking Session scheduled for 1st qtr 2023
      • Chicago Archdiocese
      • Cook County Facilities & Asset Mgmt
    • UL Healthy Buildings will become a more hands-on active participant in our iCAP effort to help expand building science expertise specific to the UL Verified Marks to also include the impacts of indoor air particulate, hazardous gases, and building hygiene:
      • SafeTraces Verified Mark for Ventilation and Filtration
      • UL Verified Mark for Healthy Buildings
  3. Update on the SafeTraces project: Astronomy Building

    Following email was sent by Sterling Laylock regarding the update:

    Hi Sarthak, Yes, we have completed the analysis and are prepared to present our findings for the Astronomy Building.

    We will also be sharing relevant data and insights from additional buildings across other regions of the state as well.

    Proposed Presentation Date

    Thursday, November 10th is our proposed date to present our findings as requested by Morgan White. 

    We also plan to conduct a Design Thinking Session that will include numerous stakeholders as requested by Senator Elgie Sims, Vice-Chair IL, Appropriations II. 

    He is seeking input regarding a strategic allocation of funding for clean indoor air assessments in K-12 and public buildings around the state in order to elevate public outreach and awareness regarding this critical issue.

    Design Thinking Stakeholder Attendees

    Primary stakeholders from outside UIUC-iCAP who have expressed a high level of interest in participating include but will not be limited to:

    • Cook County Facilities and Sustainability

    • Cook County Asset Management

    • Chicago Transit Authority

    • South Suburban Mayor and Managers

    • Catholic Archdiocese of Chicago Asset Management

    • The Obama Foundation Presidential Center

    • Sinai Chicago Health System

    • Indoor Climate Research and Training Center (ICRT)

    • Illinois Growth & Innovation Fund for Social Impact

    Why Are They Interested?

    As we all know, almost all buildings blindly struggle to have enough clean indoor air for us to breathe. 

    Stakeholders need help ending potentially harmful health and financial consequences, so people will feel safe using buildings again.

    In order to do this, we have proposed an Illinois version of the EPA Clean Air In Buildings Program using eligible American Rescue Plan (ARPA), Bipartisan Infrastructure and Inflation Reduction Act Funding. 

    Although ARPA dollars have already been allocated in IL, a significant level of funding is still scheduled to be allocated specifically for ventilation and filtration in the near term.

    sKm0HRDI9AINAKNQCPQCDQCjUAj0Ag0Ao1AI9AIrIlA319YE6hmawQagUagEWgEGoFGoBFoBBqBRqARaAQagU0R+L9h3d1F4i113QAAAABJRU5ErkJggg==

    We believe our Energy-Efficient HVAC Infection Control Project under iCAP can serve as an excellent hub for the many fragmented efforts being attempted across the state as we all seek to address this lingering pandemic and pre-pandemic issue. 

    Now that we're in the recovery period of our post-pandemic journey, it is imperative that we use this opportunity to address these issues. 

    Closing the gap between public health and building science is a key effort that will help us deliver on developing Applied Health Strategies for Climate Adaptation, which is why iCAP exists in the first place.

    Let's set a time this week to discuss our proposed date and time so we plan accordingly for a successful event.

    Thanks, Sterling

  4. HVAC and Air Quality Assessment Project Meeting (2-11-2022)

    Dhuvaraj Gambhire and Ali Khan met with Morgan White on 2-11-2022 to discuss how they can acquire a Notice to Proceed and access to the Atmospheric Science Building for testing.

    They will get a quote from Sterling, which will allow them to get a Purchase Order (PO). After they get the PO, they can get a Notice to Proceed and access to the building.

  5. Information about the occupancy schedule and Air properties of the ATMS Building

    According to F&S, Management Engineer, Mike Halm:

    1. Currently, this unit is in occupied mode on weekdays, 6AM to midnight.  Normally the occupancy schedule will more closely follow the hours the building is open, but runtimes were extended across campus as a precaution during the pandemic.

    2. When the building was originally designed, there likely wasn’t a set amount of air changes per hour applied to every classroom.  Typically for classrooms the heating and cooling airflows are determined based on the specific loads in each room, rather than applying a flat rate based on the volume of the room.  If it would help, we could share the original ventilation drawings from 1989.  Regarding the ASHRAE standards, any new construction or renovation work on campus should have mechanical ventilation provided in accordance with ASHRAE 62.1.  However, there were different codes and standards in place when this building was constructed 30 years ago.  The current version of ASHRAE 62.1 may have slightly different requirements than the codes in place when the building was built.

  6. Dhruv and Ali provided the following answers to Sterling with SafeTraces

     --------------------------------------------------------------------

    This is an example of what the format used below.

    Q#: What is the answer to this question?

    A#: This is the answer to that question.

     --------------------------------------------------------------------

     

    Dhruv and Ali provided the following answers to Sterling with SafeTraces:

     

     

    Q1: Please provide PDFs of the full floor plan layout drawings for the entire building. Be sure to include 
    square footage for each room and common areas. It is also very important to identify operable windows, if any? 

    A1: Floor plans with room areas attached. 
    Following files are attached for floor plans 
    B0300-01-11X17 Astronomy Building-(1st floor plan)-2021 
    B0300-02-11X17 Astronomy Building-(2nd Floor plan)-2021 
    (current/anticipated occupancy assumptions would be helpful) 

     

    Q2: What are the Astronomy Building's normal hours of operation?

    A2: Monday to Friday (0800 hrs-1700 hrs.). Saturday and Sunday the building is locked. 

     

    Q3: What is the air filtration rating for the spaces?

    A3: MERV :: HEPA Filters at AHU, currently MERV-13. 

     

    Q4: What is the Make/Model, age, specs and replacement/upgrade history of the existing HVAC system?

    A4: Original AHU from 1990, Trane Model 41A, Serial K89H24684. Original AHU equipment schedule attached. AHU controls originally pneumatic, upgraded to DDC (Siemens) in 2016 to allow occupancy schedules to be implemented. Zone level (VAVs) are still pneumatic.  I believe the fume hoods are only energized when in use.  Heating in the building is hot water radiators and hot water VAV reheat (no heating coil at AHU) fed from hot water boilers. 30% glycol cooling coil in AHU, fed from air cooled chiller on site. 

     

    Q5: What is the Make/Model and full specifications of the portable air purifiers expected to be used or are being used in the building? 

    A5: I don’t believe any portable air purifiers are currently in use. 

     

    Q6: Please identify all HVAC zones in the drawings. (Note: This is a command, not a question)

    A6: See zone map drawings Paul sent previously. Please review the attached file 
    CC-0300_09_V-700_RCX-Astronomy Building-Zones plan-AHU-EFU-2017 

     

    Q7: How many air-changes per hour is the HVAC system currently providing?

    A7: Will vary from room to room based on VAV damper position, ceiling height, etc. Based on a peak airflow of AHU (21,200 CFM), overall building area, and typical ceiling height (9’-0”), we’d have about 11.3 air changes per hour at peak load. 

     

    Q8: What are the basic assumptions for outside air intake to aid in dilution/ventilation for all interior spaces? 

    A8: AHU has a minimum OA position, and runs based on an occupancy schedule. We’ve temporarily changed our AHUs to run in occupied mode from 6AM to midnight for most of our units due to COVID-19 precautions. Unit is also sized for economizer when OA conditions allow. 

     

    Q9: What are the weather assumptions for heating and cooling the interior spaces along with outdoor temperature and humidity estimates?

    A9: I’m not positive what conditions the original designers used in 1990, but see page 2 of the “HVAC Systems” attachment from our facilities standards for our typical OA design conditions. 

  7. Information Needed to Establish a Framework for the Project

    The following email was sent by Sterling Laylock to Dhruvaraj Gambhire & Ali Feroz Khan.

    ----------------------------------------------------------------------

    We greatly appreciated the opportunity to meet with you today. Please find below the list of information we'll need to establish a detailed framework
    for our pilot project and pricing for full approval.

     

    We've also agreed to meet each Thursday at 4:00pm central time which will serve as our weekly meeting. There will be an exception
    to next week's meeting which will be held on Wednesday Nov 10th at 4:00pm.

     

    Building Site: Astronomy Building #0300

    Weekly Meeting Time: Thursday's 4:00-5:00pm Central

    Tasks Prior to Test Date:

    1. Test Site Floor Plan Analysis
    2. Determine Test Site Design
    3. Develop Project Protocols
    4. Establish Sampling Method
    5. Select Sampling Types, Origin Points + Intervals

    Tasks Post Test Date:

    • Lab Testing
    • Data Reporting
    • Recommendations
    • Business Case Analysis

     

    DATA and QUESTIONS: 

    Required items are highlighted in BLUE**) [note the color is not displayed on the icap portal, instead the items are starred (**)]

    Additional items are necessary, however they can be addressed later in the project timeline.

    1.     Please provide PDFs of the full floor plan layout drawings for the entire building. Be sure to include 
    square footage for each room and common areas. It is also very important to identify operable windows, if any? ** 
    (current/anticipated occupancy assumptions would be helpful)

    2.     What are the Astronomy Building's normal hours of operation? **

    3.     What is the air filtration rating for the spaces? MERV :: HEPA

    4.     Make/Model, age, specs and replacement/upgrade history of the existing HVAC system?

    5.     Make/Model and full specifications of the portable air purifiers expected to be used or are
    being used in the building.

    6.     Please identify all HVAC zones in drawings.

    7.     How many air-changes per hour is the HVAC system currently providing?

    8.     What are the basic assumptions for outside air intake to aid in dilution/ventilation for all interior spaces.

    9.     Please include weather assumptions for heating and cooling the interior spaces along with outdoor temperature and humidity estimates.

  8. ECIP Award Winners

    On October 20, 2021, the 2021 Energy Conservation Incentive Program (ECIP) Award Winners were announced at the Campus Sustainability Celebration!

    UIUC is home to a total of 10 winners and honorable mentions, as listed below according to their categories:

    • Occupant Action Category
      • Ice Arena
      • Student Dining and Residential Programs
      • English Building
      • Campus Recreation Center East (CRCE)
    • Energy Advancement Category
      • Stock Pavilion
      • Forbes Natural History Building
      • Levis Faculty Center
      • Early Development Lab
    • Honorable Mentions
      • State Farm Center
      • Bielfeldt Athletic Administrative Building

    See the attached file to read the official announcement of 2021 ECIP Winners, including the locations' % improvements and monetary savings.

    Attached Files: 
  9. 2021 Campus Sustainability Celebration!

    All are invited to the 2021 Campus Sustainability Celebration and appreciation event! Meet and network with your peer sustainability advocates and hear about exciting campus sustainability progress! Since the event is in person, please be prepared to wear a mask and show your Safer Illinois app or equivalent status. If you can't make it in person, watch the livestream on YouTube! >>>

    October 20, 1–4 pm • National Center for Supercomputing Applications lobby, 1205 W. Clark St., Urbana

    Julie Wurth • Institute for Sustainability, Energy, and Environment

    2021 Campus Sustainability Celebration!

  10. Campus Sustainability Celebration

    iSEE and F&S are excited to invite you to the Campus Sustainability Celebration 2020! This is an annual event that is especially exciting this year with the signing ceremony of the Illinois Climate Action Plan (iCAP) 2020, (once every five years) and the presentation of energy conservation and Freezer Challenge awards. Everyone is invited and encouraged to stay afterward for a social-hour!

    Campus Sustainability Celebration

    October 20, 3 pm • Map

    Meredith Moore • Institute for Sustainability, Energy, and Environment

    baseline_wifi_black_18dp.png This opportunity is available online.

  11. Energy Conservation Incentive Program - Program Update

    Hello ECIP winners,

     

    When the Energy Conservation Incentive Program (ECIP) was launched in 2013, it included financial awards that distributed some of the centrally managed campus utility funds back to the winning buildings. The calculation system was based on placement (first place to fourth place) in the awards program and the award category (occupant action or energy advancement).  You can see the calculation in the attached fact sheet from 2016, if you are interested.  With the Integrated and Value-Centered Budget (IVCB) reform, we transitioned this year, and we are closing out the initial phase one of the ECIP.

     

    Some of the original award funding has not yet been allocated to an associated facility improvement project.  If you have remaining funds and have not yet committed to a specific project, please do so as soon as possible.  All ECIP award funds must be committed by the end of this fiscal year, so please let us know your plans.

     

    Now in phase two, the ECIP awards include a plaque and the associated prestige, and no additional monetary awards (see attached revised fact sheet).  Instead, your colleges will benefit directly from the energy savings.  Additionally, to increase the visibility of the great progress all of you have made, we are collaborating with the Illinois Solar Decathlon’s Concept Team (incoming freshmen, learning about building systems and sustainability).  They will be completing a simple Building-Level Energy Report card for the 50+ ECIP winners this fall.  In the spring, I will send those reports to you with an opportunity to connect with the Concept Team members.

     

    Later this week, I will send a follow up email to the FY19 winners with images to help you spread awareness of this award.  Congratulations again to all of you, and thank you very much for your past and ongoing contributions to the campus sustainability and energy efficiency efforts.

     

    Sincerely,

    Morgan